Grid Services & IEEE-1547 Compliance
Operating Mode Selection
Grid Frequency
60.00 Hz
Grid Voltage
13.8 kV
Power Factor
0.98
THD
2.3%
Volt-VAR / Volt-Watt Curves
Fault Ride-Through Testing
Test Configuration
IEEE-1547 Compliance Status
| Requirement | Specification | Measured | Status |
|---|---|---|---|
| Voltage Regulation | ±5% | ±2.3% | ✓ PASS |
| Frequency Response | 59.3-60.5 Hz | 59.95-60.05 Hz | ✓ PASS |
| Power Factor Range | 0.85 lag - 0.85 lead | 0.90 lag - 0.90 lead | ✓ PASS |
| Voltage THD | < 5% | 2.3% | ✓ PASS |
| Current THD | < 5% | 2.8% | ✓ PASS |
| Anti-Islanding | < 2 seconds | 0.8 seconds | ✓ PASS |